SIMATIC DP, BASIC MODULE BM141 ET 200ECO: 16DI 24V DC; 8 X M12,DOUBLE-ASSIGNEMENT, DEGREE OF PROTECTION IP65/67; CONNECTING BLOCK 6ES7194-3AA00-0.A0 MUST BE ORDERED SEPARTELY |
| General information |
| Vendor identification (VendorID) |
80DAh |
| Supply voltage |
| Load voltage 1L+ |
| ● Rated value (DC) |
24 V |
| ● Reverse polarity protection |
Yes |
| Input current |
| from supply voltage 1L+, max. |
70 mA; Typical |
| Encoder supply |
| Number of outputs |
8 |
| Output voltage |
24 V DC |
| Short-circuit protection |
Yes; Electronic |
| Output current |
| ● Output current, rated value |
1 A; Aggregate current up to 55 °C |
| Power loss |
| Power loss, typ. |
3.6 W |
| Digital inputs |
| Number of digital inputs |
16 |
| Input characteristic curve in accordance with IEC 61131, type 1 |
Yes |
| Number of simultaneously controllable inputs |
| ● Number of simultaneously controllable inputs |
16; All mounting positions up to 55 °C |
| Input voltage |
| ● Type of input voltage |
DC |
| ● Rated value, DC |
24 V |
| ● for signal "1" |
13 to 30 V |
| Input current |
| ● for signal "1", typ. |
7 mA |
| Input delay (for rated value of input voltage) |
| for standard inputs |
| — at "0" to "1", max. |
3 ms; Typical |
| — at "1" to "0", max. |
3 ms; Typical |
| Cable length |
| ● Cable length unshielded, max. |
30 m |
| Encoder |
| Connectable encoders |
| ● 2-wire sensor |
Yes |
| — permissible quiescent current (2-wire sensor), max. |
1.5 mA |
| Interfaces |
| PROFIBUS DP |
| ● Transmission rate, max. |
12 Mbit/s; 9,6 / 19,2 / 45,45 / 93,75 / 187,5 / 500 kbit/s; 1,5 / 3 / 6 / 12 Mbit/s |
| Protocols |
| PROFIBUS DP |
Yes |
| Interrupts/diagnostics/status information |
| Status indicator |
Yes |
| Alarms |
| ● Alarms |
No |
| Diagnostic messages |
| ● Diagnostics |
Yes; Diagnostic information readable |
| Diagnostics indication LED |
| ● Group error SF (red) |
Yes |
| ● Status indicator digital input (green) |
Yes |
| ● Channel fault indicator F (red) |
No |
| Galvanic isolation |
| between PROFIBUS DP and all other circuit components |
Yes |
| Galvanic isolation digital inputs |
| ● between the channels |
No |
| Permissible potential difference |
| between different circuits |
75 VDC / 60 VAC |
| Isolation |
| Isolation tested with |
500 V DC |
| Dimensions |
| Width |
60 mm |
| Height |
210 mm |
| Depth |
28 mm |
| Weights |
| Weight, approx. |
210 g |
| last modified: |