SIMATIC DP, ET 200ECO PN, 8 DI 24V DC; 8 X M12, DEGREE OF PROTECTION IP67 |
| General information |
| Vendor identification (VendorID) |
002AH |
| Device identifier (DeviceID) |
0306H |
| Supply voltage |
| 24 V DC |
Yes |
| permissible range, lower limit (DC) |
20.4 V |
| permissible range, upper limit (DC) |
28.8 V |
| Reverse polarity protection |
Yes |
| Input current |
| Current consumption, typ. |
100 mA |
| Encoder supply |
| Number of outputs |
8 |
| Output current |
| ● Output current, rated value |
100 mA; per output |
| 24 V encoder supply |
| ● Short-circuit protection |
Yes |
| Power loss |
| Power loss, typ. |
4.5 W |
| Digital inputs |
| Number of digital inputs |
8 |
| ● in groups of |
1 |
| Input characteristic curve in accordance with IEC 61131, type 3 |
Yes |
| Number of simultaneously controllable inputs |
| all mounting positions |
| — up to 60 °C, max. |
8 |
| Input voltage |
| ● Type of input voltage |
DC |
| ● Rated value, DC |
24 V |
| Input current |
| ● for signal "0", max. (permissible quiescent current) |
1.5 mA |
| ● for signal "1", typ. |
7 mA |
| Input delay (for rated value of input voltage) |
| for standard inputs |
| — at "0" to "1", max. |
typically 3 ms |
| — at "1" to "0", max. |
typically 3 ms |
| Cable length |
| ● Cable length unshielded, max. |
30 m |
| Interfaces |
| Transmission procedure |
100BASE-TX |
| Transmission rate, max. |
100 Mbit/s |
| PROFINET IO |
| ● Number of PROFINET interfaces |
1 |
| ● Autocrossing |
Yes |
| ● automatic detection of transmission rate |
Yes |
| ● integrated switch |
Yes |
| PROFINET IO Device |
| — IRT with the option "high flexibility", supported |
Yes |
| — Prioritized startup |
Yes |
| Protocols |
| PROFINET IO |
Yes |
| PROFINET CBA |
No |
| PROFIsafe |
No |
| Protocols (Ethernet) |
| ● SNMP |
Yes |
| ● DCP |
Yes |
| ● LLDP |
Yes |
| ● ping |
Yes |
| ● ARP |
Yes |
| Interrupts/diagnostics/status information |
| Status indicator |
Yes; Green LED |
| Alarms |
| ● Diagnostic alarm |
Yes |
| Diagnostic messages |
| ● Diagnostic functions |
Yes |
| ● Diagnostic information readable |
Yes |
| ● Monitoring the supply voltage |
Yes; Green "ON" LED |
| ● Wire-break in signal transmitter cable |
Yes |
| ● Short-circuit encoder supply |
Yes; Per channel group |
| ● Group error |
Yes; Red/yellow "SF/MT" LED |
| Galvanic isolation |
| between the load voltages |
Yes |
| between load voltage and all other switching components |
No |
| between Ethernet and electronics |
Yes |
| Galvanic isolation digital inputs |
| ● between the channels |
No |
| Permissible potential difference |
| between different circuits |
75 VDC / 60 VAC |
| Isolation |
| tested with |
| ● 24 V DC circuits |
500 V |
| ● Interface |
1 500 V; According to IEEE 802.3 |
| Degree and class of protection |
| IP65 |
Yes |
| IP66 |
Yes |
| IP67 |
Yes |
| Connection method |
| M12 |
Yes |
| Dimensions |
| Width |
60 mm |
| Height |
175 mm |
| Depth |
49 mm |
| Weights |
| Weight (without packaging) |
910 g |
| last modified: |
21.08.2014 |