SIMATIC DP, BASIC MODULE BM142 ET 200ECO: 8 DO DC 24 V/2 A; 8 X M12, SINGLE-ASSIGNEMENT, DEGREE OF PROTECTION IP65/67; CONNECTING BLOCK 6ES7194-3AA00-0.A0 MUST BE ORDERED SEPARTELY |
| General information |
| Vendor identification (VendorID) |
80DDh |
| Supply voltage |
| Load voltage 1L+ |
| ● Rated value (DC) |
24 V |
| ● Reverse polarity protection |
Yes |
| Load voltage 2L+ |
| ● Rated value (DC) |
24 V |
| ● Reverse polarity protection |
Yes |
| Input current |
| from load voltage 2L+ (without load), max. |
60 mA; Typical |
| from supply voltage 1L+, max. |
70 mA; Typical |
| Power loss |
| Power loss, typ. |
4 W |
| Digital outputs |
| Number of digital outputs |
8 |
| Short-circuit protection |
Yes |
| ● Response threshold, typ. |
4 A per channel |
| Limitation of inductive shutdown voltage to |
2L+ (-44 V) |
| Controlling a digital input |
Yes |
| Switching capacity of the outputs |
| ● Lamp load, max. |
10 W |
| Load resistance range |
| ● lower limit |
12 Ω |
| ● upper limit |
4 kΩ |
| Output voltage |
| ● for signal "1", min. |
2L+ (-0,8 V) |
| Output current |
| ● for signal "1" rated value |
2 A |
| ● for signal "1" permissible range for 0 to 55 °C, min. |
5 mA |
| ● for signal "1" permissible range for 0 to 55 °C, max. |
2.4 A |
| ● for signal "0" residual current, max. |
0.5 mA |
| Parallel switching of 2 outputs |
| ● for uprating |
No |
| ● for redundant control of a load |
Yes |
| Switching frequency |
| ● with resistive load, max. |
100 Hz |
| ● with inductive load, max. |
0.5 Hz; to IEC 947-5-1, DC-13 |
| ● on lamp load, max. |
1 Hz |
| Total current of the outputs (per group) |
| all mounting positions |
| — up to 55 °C, max. |
4 A; 4 A each for sockets X1, X3, X5, X7 and 4 A each for sockets X2, X4, X6, X8; note the current carrying capacity of the cable |
| Cable length |
| ● Cable length unshielded, max. |
30 m |
| Interfaces |
| PROFIBUS DP |
| ● Transmission rate, max. |
12 Mbit/s; 9,6 / 19,2 / 45,45 / 93,75 / 187,5 / 500 kbit/s; 1,5 / 3 / 6 / 12 Mbit/s |
| Protocols |
| PROFIBUS DP |
Yes |
| Interrupts/diagnostics/status information |
| Status indicator |
Yes |
| Alarms |
| ● Alarms |
No |
| Diagnostic messages |
| ● Diagnostics |
Yes; Diagnostic information readable |
| Diagnostics indication LED |
| ● Group error SF (red) |
Yes |
| ● Status indicator digital output (green) |
Yes |
| ● Channel fault indicator F (red) |
No |
| Galvanic isolation |
| between PROFIBUS DP and all other circuit components |
Yes |
| Galvanic isolation digital outputs |
| ● between the channels |
No |
| Permissible potential difference |
| between different circuits |
75 VDC / 60 VAC |
| Isolation |
| Isolation tested with |
500 V DC |
| Dimensions |
| Width |
60 mm |
| Height |
210 mm |
| Depth |
28 mm |
| Weights |
| Weight, approx. |
210 g |
| last modified: |