SIMATIC DP, ET 200ECO PN, 8 AI (4 U/I + 4 RTD/TC); 8XM12, DEGREE OF PROTECTION IP67 |
| General information |
| Vendor identification (VendorID) |
002AH |
| Device identifier (DeviceID) |
0306H |
| Supply voltage |
| 24 V DC |
Yes |
| permissible range, lower limit (DC) |
20.4 V |
| permissible range, upper limit (DC) |
28.8 V |
| Reverse polarity protection |
Yes |
| Input current |
| Current consumption, typ. |
110 mA |
| Encoder supply |
| Number of outputs |
4 |
| 24 V encoder supply |
| ● Short-circuit protection |
Yes; Electronic at 1.4 A |
| ● Output current, max. |
1 A |
| Power loss |
| Power loss, typ. |
2.8 W |
| Analog inputs |
| Number of analog inputs |
8 |
| Number of analog inputs for voltage/current measurement |
4 |
| Number of analog inputs for resistance/resistance thermometer measurement |
4 |
| permissible input voltage for voltage input (destruction limit), max. |
28.8 V permanent, 35 V for max. 500 ms |
| Input ranges (rated values), voltages |
| ● 0 to +10 V |
Yes |
| ● 1 to 5 V |
Yes |
| ● -10 V to +10 V |
Yes |
| ● -80 mV to +80 mV |
Yes |
| Input ranges (rated values), currents |
| ● 0 to 20 mA |
Yes |
| ● -20 to +20 mA |
Yes |
| ● 4 to 20 mA |
Yes |
| Input ranges (rated values), thermocouples |
| ● Type E |
Yes |
| ● Type J |
Yes |
| ● Type K |
Yes |
| ● Type N |
Yes |
| Input ranges (rated values), resistance thermometers |
| ● Ni 100 |
Yes |
| ● Ni 1000 |
Yes |
| ● Ni 120 |
Yes |
| ● Ni 200 |
Yes |
| ● Ni 500 |
Yes |
| ● Pt 100 |
Yes |
| ● Pt 1000 |
Yes |
| ● Pt 200 |
Yes |
| ● Pt 500 |
Yes |
| Input ranges (rated values), resistors |
| ● 0 to 150 Ohm |
Yes |
| ● 0 to 300 Ohm |
Yes |
| ● 0 to 600 Ohm |
Yes |
| ● 0 to 3000 Ohm |
Yes |
| Thermocouple (TC) |
| Temperature compensation |
| — parameterizable |
Yes |
| — internal temperature compensation |
Yes |
| — external temperature compensation with compensations socket |
Yes |
| Cable length |
| ● Cable length, shielded, max. |
30 m |
| Analog value generation |
| Analog value display |
SIMATIC S7 format |
| Measurement principle |
integrating |
| Integration and conversion time/resolution per channel |
| ● Resolution (incl. overrange) |
15 bits + sign |
| ● Integration time, parameterizable |
Yes |
| ● Integration time, ms |
2/16.67/20/100 ms |
| ● Interference voltage suppression for interference frequency f1 in Hz |
500 / 60 / 50 / 10 Hz |
| ● Conversion time (per channel) |
4 / 19 / 22 / 102 ms |
| Smoothing of measured values |
| ● parameterizable |
Yes |
| ● Step: None |
Yes; 1 x cycle time |
| ● Step: Low |
Yes; 4 x cycle time |
| ● Step: Medium |
Yes; 16 x cycle time |
| ● Step: High |
Yes; 64 x cycle time |
| Encoder |
| Number of connectable encoders, max. |
8 |
| Connection of signal encoders |
| ● for voltage measurement |
Yes |
| ● for current measurement as 2-wire transducer |
Yes |
| ● for current measurement as 4-wire transducer |
Yes |
| ● for resistance measurement with two-wire connection |
Yes |
| ● for resistance measurement with three-wire connection |
Yes |
| ● for resistance measurement with four-wire connection |
Yes |
| Errors/accuracies |
| Linearity error (relative to input range), (+/-) |
0.01 % |
| Temperature error (relative to input range), (+/-) |
U: 0.0035%/°C; I:0.006%/°C; RTD: 0.0005%/°C; TC: 0.0035%/°C |
| Crosstalk between the inputs, min. |
85 dB |
| Repeat accuracy in steady state at 25 °C (relative to input area), (+/-) |
0.008 % |
| Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency |
| ● Series mode interference (peak value of interference < rated value of input range), min. |
46 dB |
| ● Common mode interference, min. |
70 dB |
| Interfaces |
| Transmission procedure |
100BASE-TX |
| Transmission rate, max. |
100 Mbit/s |
| PROFINET IO |
| ● Number of PROFINET interfaces |
1 |
| ● Autocrossing |
Yes |
| ● automatic detection of transmission rate |
Yes |
| ● integrated switch |
Yes |
| PROFINET IO Device |
| — IRT with the option "high flexibility", supported |
Yes |
| — Prioritized startup |
Yes |
| Protocols |
| PROFINET IO |
Yes |
| PROFINET CBA |
No |
| PROFIsafe |
No |
| Protocols (Ethernet) |
| ● SNMP |
Yes |
| ● DCP |
Yes |
| ● LLDP |
Yes |
| ● ping |
Yes |
| ● ARP |
Yes |
| Interrupts/diagnostics/status information |
| Status indicator |
Yes |
| Alarms |
| ● Diagnostic alarm |
Yes |
| Diagnostic messages |
| ● Diagnostic functions |
Yes |
| ● Diagnostic information readable |
Yes |
| ● Monitoring the supply voltage |
Yes; Green "ON" LED |
| ● Short-circuit encoder supply |
Yes; per module |
| ● Group error |
Yes; Red/yellow "SF/MT" LED |
| ● Overflow/underflow |
Yes |
| Galvanic isolation |
| between the load voltages |
Yes |
| between load voltage and all other switching components |
No |
| between Ethernet and electronics |
Yes |
| Galvanic isolation analog inputs |
| ● between the channels |
No |
| Permissible potential difference |
| between inputs and MANA (UCM) |
10 Vpp AC |
| Isolation |
| tested with |
| ● 24 V DC circuits |
500 V |
| ● Interface |
1 500 V; According to IEEE 802.3 |
| Degree and class of protection |
| IP65 |
Yes |
| IP66 |
Yes |
| IP67 |
Yes |
| Connection method |
| M12 |
Yes |
| Dimensions |
| Width |
60 mm |
| Height |
175 mm |
| Depth |
49 mm |
| Weights |
| Weight (without packaging) |
930 g |
| last modified: |
21.08.2014 |