SIMATIC DP, ELECTRONIC MODULES FOR ET200PRO 8 DO DC 24V, 0.5A MODULE DIAGNOSTICS; INCLUSIVE BUS MODULE, CONNECTING MODULE IO 6ES7194-4..00-0AA0 MUST BE ORDERED SEPERATELY |
| FH technology |
| Module for fail-safe applications |
No |
| Supply voltage |
| Load voltage 2L+ |
| ● Rated value (DC) |
24 V |
| ● Short-circuit protection |
Yes; per channel, electronic |
| ● Reverse polarity protection |
Yes; against destruction; load increasing |
| Input current |
| from load voltage 2L+ (without load), max. |
30 mA |
| from backplane bus 3.3 V DC, max. |
30 mA |
| Power loss |
| Power loss, typ. |
2 W |
| Address area |
| Address space per module |
| ● with packing |
8 bit |
| ● without packing |
1 byte |
| Digital outputs |
| Number of digital outputs |
8 |
| Short-circuit protection |
Yes |
| ● Response threshold, typ. |
0,7 |
| Limitation of inductive shutdown voltage to |
2L+ (-47 V) |
| Controlling a digital input |
Yes; Isolation between 1L+ and 2L+ is no longer provided, as 1M and 2M are jumpered |
| Switching capacity of the outputs |
| ● Lamp load, max. |
5 W |
| Load resistance range |
| ● lower limit |
48 Ω |
| ● upper limit |
4 kΩ |
| Output voltage |
| ● for signal "1", min. |
2L+ (-0,8 V) |
| Output current |
| ● for signal "1" rated value |
0.5 A |
| ● for signal "0" residual current, max. |
0.5 mA |
| Parallel switching of 2 outputs |
| ● for uprating |
No |
| ● for redundant control of a load |
Yes |
| Switching frequency |
| ● with resistive load, max. |
100 Hz |
| ● with inductive load, max. |
0.5 Hz |
| ● on lamp load, max. |
1 Hz |
| Total current of the outputs (per group) |
| all mounting positions |
| — up to 55 °C, max. |
4 A |
| Cable length |
| ● Cable length, shielded, max. |
30 m |
| ● Cable length unshielded, max. |
30 m |
| Interrupts/diagnostics/status information |
| Diagnostic messages |
| ● Diagnostic functions |
Yes |
| ● Diagnostic information readable |
Yes |
| ● Short-circuit |
Yes; Short-circuit of outputs to ground; module by module |
| Diagnostics indication LED |
| ● Group error SF (red) |
Yes |
| ● Status indicator digital output (green) |
Yes |
| Galvanic isolation |
| Galvanic isolation digital outputs |
| ● between the channels |
No |
| ● between the channels and the backplane bus |
Yes |
| Isolation |
| Isolation tested with |
500 V DC |
| Dimensions |
| Width |
45 mm |
| Height |
130 mm |
| Depth |
35 mm |
| Weights |
| Weight, approx. |
140 g |